LK Automation Limited
Home >> Products >> OMRON >> Master slave station products >> DeviceNet >> GT1-ID16ML-1 I/O classification: Digital input OMRON GT1-ID16ML-1

GT1-ID16ML-1 I/O classification: Digital input OMRON GT1-ID16ML-1

Brand: OMRON
Name: Digital I/O Units
Model: GT1-ID16ML-1
Unit: Connector model.
I/O classification: Digital input.
Internal I/O common: PNP (- common).
I/O points: 16.
I/O connections: Fujitsu connector.
Power supplyvoltage: 24 VDC.
I/O specification: DC/transistor.
Digital I/O Units Compatible with MULTIPLE I/O TERMINAL,
Terminal block, connector, and high-density connector,
models are available.
The circuit block of the terminal block model can be,
mounted or dismounted for ease of maintenance without,
disconnecting the wires.
DIN track mounting.

Name: Compact Connectors.
Specifications: Inputs/Outputs; 2 input/2 output; PNP.
Bit slave of smallest class in industry,
Innovation in wiring for any type of machinery.
Available in 2 types: 2-point Bit Slave Unit,
and 4-point Bit Slave Unit.
Compact size for installation in limited space.
Save space and wiring since bit slave can be,
installed near I/O devices OMRON GT1-ID16ML-1.
Industry first bit slave connectable with round,
cables which can be easily purchased at a lower price GT1-ID16ML-1
Connectable with flat cables, too for easy wiring.
Cables are selectable depending on applications. Short/disconnection detection: Supported.
Specifications: Inputs, NPN (+ common), 16 points.
I/O connections: Clamp terminals OMRON GT1-ID16ML-1.
Rated internal circuit power supply voltage:
Supplied from communications connector.
Rated I/O power supply voltage: 24 VDC.
Reduced Wiring and Labor on Factory Sites with Screw-less Terminal Wiring.
Screw-less structure eliminates tightening work.
Detachable terminal blocks for easier maintenance.
Single-step wiring by simply inserting pole terminals. Input capacity: 16 points OMRON GT1-ID16ML-1.
Rated current (ON current):
0.5 A/output, 4.0 A/common.
Internal I/O common: PNP.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the V terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max OMRON Digital I/O Units.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation OMRON Digital I/O Units.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled OMRON Digital I/O Units.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit GT1-ID16ML-1. )
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary sswitch and with tool software OMRON GT1-ID16ML-1.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.