Mitsubishi L60ADIL8-CM Analog Input Module – 8-Channel High-Speed Isolated Specifications & Wiring Guide
Mitsubishi Analog Input Module L60ADIL8-CM
Mitsubishi Analog Input Module L60ADIL8-CM
●Channels: 8
●Input current: DC 0–20 mA
●Conversion speed: 1 ms/ch
●Resolution: 1/8000
●Shift function: enables fine adjustment during system startup by adding a set shift value to digital output; changes reflect in real time on scaled values
●Extended input signal anomaly detection: supports lower/upper limit detection or wire break detection
●Extended input range function: expands input range, facilitates wire break detection when combined with anomaly detection
Mitsubishi Analog Input Module L60ADIL8-CM
The L60ADIL8-CM is a high-performance analog input module designed for Mitsubishi MELSEC-L series PLCs, offering 8 independent input channels for flexible process control and data acquisition applications.
Key Specifications:
●Input Channels: 8 channels (isolated)
●Input Signal Type: DC current, 0 to 20 mA
●Conversion Speed: 1 ms per channel (fast sampling for real-time control)
●Resolution: 1/8000 (equivalent to 13-bit resolution, providing high-precision measurement)
Advanced Shift Function for System Startup Tuning:
The module features a built-in shift function that allows users to apply a programmable offset value to the digital output value. This offset, known as the conversion value shift amount, is added to the scaled digital output in real time. This enables operators to perform fine adjustments during system commissioning or startup without reprogramming or halting the process. Any changes made to the shift value are immediately reflected in the scaled output, significantly simplifying calibration and troubleshooting procedures.
Extended Input Signal Anomaly Detection:
To enhance diagnostic capabilities, the module supports an expanded input signal anomaly detection function. In addition to the standard upper/lower limit detection, users can configure the module to detect only upper-limit deviations, only lower-limit deviations, or both as required. This flexibility is particularly useful for applications where only one-sided monitoring is necessary, or where specific fault conditions such as wire breaks need to be identified. The detection settings can be tailored per channel, enabling precise and efficient fault isolation.
Input Range Expansion Function:
The module also offers an input range expansion function, which extends the measurable span of the input signal beyond the standard 0–20 mA range. This feature is especially beneficial when combined with the anomaly detection function, as it allows the system to reliably detect wire break conditions (e.g., when the input current drops to a value outside the normal operating range). The expanded range capability ensures robust monitoring in industrial environments where signal integrity is critical.
General Benefits:
●High-speed conversion (1 ms/ch) ensures minimal delay in control loops.
●8-channel design reduces panel space and wiring complexity.
●Isolated inputs improve noise immunity and protect the PLC from field-side disturbances.
●Flexible configuration options allow adaptation to diverse process requirements.
●Real-time adjustability minimizes downtime during commissioning and maintenance.
Have questions about industrial components? We'd love to hear from you.
Our experts are ready to assist you in finding the right parts for your industrial automation needs.